Allen-Bradley
XM-124 Standard Dynamic Measurement Mdl
MFG #1440-SDM02-01RA
$4,203.49 / E
EACH
EACH
Product Description:
1440-SDM02-01RA: XM-124 Standard Dynamic Measurement Module
HESCO Part Number
AB1440SDM0201RA
UPC
884951743045
Manufacturer Part Number
1440-SDM02-01RA
Manufacturer
Allen-Bradley
Allen-Bradley
XM-124 Standard Dynamic Measurement Mdl
MFG #1440-SDM02-01RA
Product Description:
1440-SDM02-01RA: XM-124 Standard Dynamic Measurement Module
HESCO Part Number
AB1440SDM0201RA
UPC
884951743045
Manufacturer Part Number
1440-SDM02-01RA
Manufacturer
Allen-Bradley
$4,203.49 / E
EACH
EACH
- Features
- Specifications
- Resources
- China CCC
- 2 output
- ATEX
- IEPE Accel, ECP's, Volts transducer power
- ±1% of full scale range for the channel, ±1% of alarm setpoint for speed
- Any measured param alarm parameters
- Independently configured per channel, Frequency, min 25.1000 Hz, Frequency, max 100…5500 Hz, Roll off: -60 dB/octave
- One active buffer per dynamic channel, One resistive buffer for tachom
General Features
| Output | : | 2 |
| Transducer Power | : | IEPE Accel, ECP's, Volts |
| Nonvolatile configuration | : | A copy of the module configuration is retained in nonvolatile memory from which the configuration is loaded upon powerup, The configuration that is stored in nonvolatile memory can be deleted only by a module-reset,command that is sent via a serial interf |
| Status indicator | : | Module, Network, Channel 1, Channel 2, Tachom, Setpoint multiplier, Virtual relay |
Inputs Outputs Io | ||
| 4...20 mA outputs | : | Each output is independently progmed to represent any measured param, from either channel, Two isolated outputs, 300 Ω max load |
| Buffered outputs | : | One active buffer per dynamic channel, One resistive buffer for tachom |
| Sensitivity | : | Up to 15% from nom |
| Two dynamic channel inputs | : | Eddy current transducer signals, Accelerom signals, Voltage signals from any dynamic measurement sensor, such as velocity or pressure transducer |
| Voltage ranges | : | -20…0V DC, -10.10V DC, 0…20V DC |
Power Electrical Characteristics | ||
| Ethernet | : | false |
| Isolation voltage | : | 50V (continuous), basic insulation type between uninsulated live parts and the enclosure with the relay contacts open and closed, Type tested at 707V DC @ 60s between uninsulated live parts and the enclosure with the relay contacts open and closed, Typ |
| Model | : | Basic device |
| Number of indicator outputs | : | 7 |
| Suitable for bus connection | : | true |
| Type of electric connection | : | Screw connection |
| Voltage type of supply voltage | : | DC |
Communication Interfaces | ||
| DeviceNet network | : | Standard DeviceNet protocol for all functions (not power-module power is provided independently), Available EDS file supports most DeviceNet compliant systems, Communication rate that is set automatically by bus master to 125 Kbps, 250 Kbps, or 500 Kbps, |
| Serial | : | RS-232 via mini-connector or terminal base unit, Communication rate that is fixed at 19.2 Kbps, Local configuration via the Serial Configuration Utility |
Measurement Parameters | ||
| FFT derived | : | FFT bands, Four bands per channel, Defined in frequency or order domain, Overall or max peak in band, Orders, Magnitude: 1x, 2x, 3x, Phase: 1x, 2x, Not 1x, Sum harmonics |
| Real time | : | Overall, RMS, Peak (true or calculated), Peak-to-peak (true or calculated), gSE, Optional low pass filter, -3 dB corner: 200 Hz.20 kHz, Roll off: -24 dB/octave, Gap (or transducer bias voltage), Speed, SMAX magnitude, SMAX phase, Band pass filter value, |
| Type | : | FFT and time waveform, Asynchronous or synchronous |
Tachometer Input | ||
| Input impedance | : | >120 kΩ |
| One tachometer input | : | ±25V (50V max peak-to-peak), 1.50,000 events/revolution |
| Pulses per revolution | : | 0 (tach off)…50,000 |
| Range | : | 1.1,200,000 rpm, 0.0167…20,000 Hz |
| Rate of change of speed, max | : | 500 Hz/s |
Construction | ||
| Enclosure type rating | : | None (open-style) |
| Modular expandable | : | true |
| Type of fastening | : | Direct mounting |
Mechanical | ||
| Weight | : | Module: 0.172 kg (0.38 lb), Terminal base: 0.172 kg (0.38 lb) |
Relays Control Outputs | ||
| Activation on | : | Alarm Status: Normal, Alert, Danger, Disarm, Transducer fault, Module fault, Tacho fault |
| Logic | : | Single or paired AND or OR logic that is applied to any alarm |
| Peak speed capture | : | The XM-124 retains the value of the highest speed that is observed since module power was cycled or the peak speed value was manually reset |
| Reset | : | Local reset switch on top of module, Remote reset switch that is wired to terminal base, Digital reset command via serial or DeviceNet interface |
| Time delay | : | 0…25.5 s, adjustable in 100 ms increments |
Alarms Fault Management | ||
| Alarm parameters | : | Any measured param |
| Failsafe | : | Normally energized (fail-safe), Normally de-energized (non-failsafe) |
| Hysteresis | : | User configurable in software |
| Latching | : | Latching, non-latching |
| Number | : | Sixteen alarm and danger pairs |
| Operators | : | Greater than, Less than, Inside range, Outside range |
| Speed inhibit | : | A speed range can be specified for each alarm. When applied, the alarm is disabled when speed is outside of the defined range |
| Startup inhibit/setpoint multiplication | : | Period: 0.1092 min, adjustable in 0.1 min increments, Inhibit/multiplication function, Multiply by N (0.10, 0 = Disarm) |
Signal Processing Conditioning | ||
| Band pass digital filter | : | Independently configured per channel, Frequency, min 25.1000 Hz, Frequency, max 100…5500 Hz, Roll off: -60 dB/octave |
| FFT lines | : | 100, 200, 400, 800, 1600 |
| High pass analog filters | : | -3 dB corners: 0.2, 1, 5, 10, 40 Hz, Roll off: -30 dB/octave for the 0.2 Hz filter, otherwise 24 dB/octave |
| Integration | : | None, single or double |
| Low pass analog filter | : | Applied to integrated acceleration measurements, -3 dB corner: 5 kHz, roll off: -18 dB/octave |
| Low pass digital filter | : | Independently configured per channel, Optional Overall LP Filter, 100.20000 Hz, Spike Energy, Spectra FMAX: 10.5000 Hz, Roll Off: -24 dB/octave |
| Resolution | : | A/D conversion: 24 bit, Dynamic range: 80 dbfs (0.01% fs), 90 dbfs, typical |
| Sampling mode | : | Selectable per channel, Dynamic Measurements, Asynchronous, FMAX: 1 Hz…20 kHz, Synchronous, Order range: 4…200, FMAX: 10 Hz…5000 Hz, Measured: orders x speed (Hz), Spike Energy, Static Measurements, Eccentricity, Peak-to-Peak Eccentricity, Thrust, Normal |
| Tracking digital filter | : | Independently configured per channel, Tracked speed multiple: 0.1.20.0 times the measured (tachom) rpm, Constant Q: 1.200, Constant bandwidth: 0.1.25 Hz, Roll off: -36 dB/octave, Typical |
| Units | : | g, ips, mm/s, mils, µm, PSI, mbar, volt |
Standards Protection | ||
| Conducted RF immunity | : | 10V rms with 1 kHz sine-wave 80% AM from 150 kHz.80 MHz |
| EFT/B immunity | : | ±3kV @ 5kHz on power ports, ±3kV @ 5kH on signal ports, ±3kV @ 5kHz on DeviceNet ports |
| Emissions | : | Class A |
| ESD immunity | : | 6 kV contact discharges, 8 kV air discharges |
| Operating temperature | : | -20 °C |
| Radiated RF immunity | : | 10 V/m with 1 kHz sine-wave 80% AM from 80.2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000.2700 MHz |
| Relative humidity | : | 5.95% noncondensing |
| Shock | : | opsal: 15 G |
| Storage temperature | : | -40 °C |
| Surge transient immunity | : | ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power and relay ports, ±2 kV line-earth (CM) on shielded signal ports, ±2 kV line-earth (CM) on DeviceNet ports |
| Vibration | : | 5 G @ 10.500 Hz |
Overview | ||
| Standard Warranty Duration | : | 1 year |
Specifications | ||
| 4...20 mA outputs | : | Each output is independently progmed to represent any measured param, from either channel, Two isolated outputs, 300 Ω max load |
| Alarm Status | : | Normal, Alert, Danger, Disarm, Transducer fault, Module fault, Tacho fault |
| Build America, Buy America | : | No |
| Repair Options Available | : | No |
| Depth | : | 94 mm |
| Expected life | : | Mechanical: 2x10^7, Electrical @ 20 cpm, 1.5A @ 24V DC: 10^5 |
| Height | : | 97 mm |
| Rating | : | Capacity, nominal: 1.5A @ 24V DC, Capacity, min 100 µA @ 100 mV DC, Power, max 41.4 W, Voltage, max 27.6V DC, Current, max 1.5 A |
| Width | : | 94 mm |
| Country of Origin | : | United States |
Module | ||
| Power dissipation, max | : | 8.7 W |
| Power supply | : | 24V DC @ 350mA, Requires Class 2/SELV/PELV power supply |
| Wiring category | : | 2 - on signal ports, 1 - on power and relay ports, 2 - on DeviceNet ports, 3 - on serial ports |
Data Handling | ||
| Accuracy, min | : | ±1% of full scale range for the channel, ±1% of alarm setpoint for speed |
| Complex data | : | Spectra (synchronous or asynchronous), Waveform (synchronous or asynchronous), Simultaneous waveforms (synchronous), gSE Spectra |
| Delta time buffer | : | Number of records: 2048, Delta time interval: 1…3600 s, Trigger mode: Relay is activated or trigger event (such as DeviceNet command from a controller or host) |
| Spectra or waveform | : | Saved upon same trigger as delta time buffer |
- China CCC
- 2 output
- ATEX
- IEPE Accel, ECP's, Volts transducer power
- ±1% of full scale range for the channel, ±1% of alarm setpoint for speed
- Any measured param alarm parameters
- Independently configured per channel, Frequency, min 25.1000 Hz, Frequency, max 100…5500 Hz, Roll off: -60 dB/octave
- One active buffer per dynamic channel, One resistive buffer for tachom
General Features
Output : 2 Transducer Power : IEPE Accel, ECP's, Volts Nonvolatile configuration : A copy of the module configuration is retained in nonvolatile memory from which the configuration is loaded upon powerup, The configuration that is stored in nonvolatile memory can be deleted only by a module-reset,command that is sent via a serial interf Status indicator : Module, Network, Channel 1, Channel 2, Tachom, Setpoint multiplier, Virtual relay Inputs Outputs Io
4...20 mA outputs : Each output is independently progmed to represent any measured param, from either channel, Two isolated outputs, 300 Ω max load Buffered outputs : One active buffer per dynamic channel, One resistive buffer for tachom Sensitivity : Up to 15% from nom Two dynamic channel inputs : Eddy current transducer signals, Accelerom signals, Voltage signals from any dynamic measurement sensor, such as velocity or pressure transducer Voltage ranges : -20…0V DC, -10.10V DC, 0…20V DC Power Electrical Characteristics
Ethernet : false Isolation voltage : 50V (continuous), basic insulation type between uninsulated live parts and the enclosure with the relay contacts open and closed, Type tested at 707V DC @ 60s between uninsulated live parts and the enclosure with the relay contacts open and closed, Typ Model : Basic device Number of indicator outputs : 7 Suitable for bus connection : true Type of electric connection : Screw connection Voltage type of supply voltage : DC Communication Interfaces
DeviceNet network : Standard DeviceNet protocol for all functions (not power-module power is provided independently), Available EDS file supports most DeviceNet compliant systems, Communication rate that is set automatically by bus master to 125 Kbps, 250 Kbps, or 500 Kbps, Serial : RS-232 via mini-connector or terminal base unit, Communication rate that is fixed at 19.2 Kbps, Local configuration via the Serial Configuration Utility Measurement Parameters
FFT derived : FFT bands, Four bands per channel, Defined in frequency or order domain, Overall or max peak in band, Orders, Magnitude: 1x, 2x, 3x, Phase: 1x, 2x, Not 1x, Sum harmonics Real time : Overall, RMS, Peak (true or calculated), Peak-to-peak (true or calculated), gSE, Optional low pass filter, -3 dB corner: 200 Hz.20 kHz, Roll off: -24 dB/octave, Gap (or transducer bias voltage), Speed, SMAX magnitude, SMAX phase, Band pass filter value, Type : FFT and time waveform, Asynchronous or synchronous Tachometer Input
Input impedance : >120 kΩ One tachometer input : ±25V (50V max peak-to-peak), 1.50,000 events/revolution Pulses per revolution : 0 (tach off)…50,000 Range : 1.1,200,000 rpm, 0.0167…20,000 Hz Rate of change of speed, max : 500 Hz/s Construction
Enclosure type rating : None (open-style) Modular expandable : true Type of fastening : Direct mounting Mechanical
Weight : Module: 0.172 kg (0.38 lb), Terminal base: 0.172 kg (0.38 lb) Relays Control Outputs
Activation on : Alarm Status: Normal, Alert, Danger, Disarm, Transducer fault, Module fault, Tacho fault Logic : Single or paired AND or OR logic that is applied to any alarm Peak speed capture : The XM-124 retains the value of the highest speed that is observed since module power was cycled or the peak speed value was manually reset Reset : Local reset switch on top of module, Remote reset switch that is wired to terminal base, Digital reset command via serial or DeviceNet interface Time delay : 0…25.5 s, adjustable in 100 ms increments Alarms Fault Management
Alarm parameters : Any measured param Failsafe : Normally energized (fail-safe), Normally de-energized (non-failsafe) Hysteresis : User configurable in software Latching : Latching, non-latching Number : Sixteen alarm and danger pairs Operators : Greater than, Less than, Inside range, Outside range Speed inhibit : A speed range can be specified for each alarm. When applied, the alarm is disabled when speed is outside of the defined range Startup inhibit/setpoint multiplication : Period: 0.1092 min, adjustable in 0.1 min increments, Inhibit/multiplication function, Multiply by N (0.10, 0 = Disarm) Signal Processing Conditioning
Band pass digital filter : Independently configured per channel, Frequency, min 25.1000 Hz, Frequency, max 100…5500 Hz, Roll off: -60 dB/octave FFT lines : 100, 200, 400, 800, 1600 High pass analog filters : -3 dB corners: 0.2, 1, 5, 10, 40 Hz, Roll off: -30 dB/octave for the 0.2 Hz filter, otherwise 24 dB/octave Integration : None, single or double Low pass analog filter : Applied to integrated acceleration measurements, -3 dB corner: 5 kHz, roll off: -18 dB/octave Low pass digital filter : Independently configured per channel, Optional Overall LP Filter, 100.20000 Hz, Spike Energy, Spectra FMAX: 10.5000 Hz, Roll Off: -24 dB/octave Resolution : A/D conversion: 24 bit, Dynamic range: 80 dbfs (0.01% fs), 90 dbfs, typical Sampling mode : Selectable per channel, Dynamic Measurements, Asynchronous, FMAX: 1 Hz…20 kHz, Synchronous, Order range: 4…200, FMAX: 10 Hz…5000 Hz, Measured: orders x speed (Hz), Spike Energy, Static Measurements, Eccentricity, Peak-to-Peak Eccentricity, Thrust, Normal Tracking digital filter : Independently configured per channel, Tracked speed multiple: 0.1.20.0 times the measured (tachom) rpm, Constant Q: 1.200, Constant bandwidth: 0.1.25 Hz, Roll off: -36 dB/octave, Typical Units : g, ips, mm/s, mils, µm, PSI, mbar, volt Standards Protection
Conducted RF immunity : 10V rms with 1 kHz sine-wave 80% AM from 150 kHz.80 MHz EFT/B immunity : ±3kV @ 5kHz on power ports, ±3kV @ 5kH on signal ports, ±3kV @ 5kHz on DeviceNet ports Emissions : Class A ESD immunity : 6 kV contact discharges, 8 kV air discharges Operating temperature : -20 °C Radiated RF immunity : 10 V/m with 1 kHz sine-wave 80% AM from 80.2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000.2700 MHz Relative humidity : 5.95% noncondensing Shock : opsal: 15 G Storage temperature : -40 °C Surge transient immunity : ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power and relay ports, ±2 kV line-earth (CM) on shielded signal ports, ±2 kV line-earth (CM) on DeviceNet ports Vibration : 5 G @ 10.500 Hz Overview
Standard Warranty Duration : 1 year Specifications
4...20 mA outputs : Each output is independently progmed to represent any measured param, from either channel, Two isolated outputs, 300 Ω max load Alarm Status : Normal, Alert, Danger, Disarm, Transducer fault, Module fault, Tacho fault Build America, Buy America : No Repair Options Available : No Depth : 94 mm Expected life : Mechanical: 2x10^7, Electrical @ 20 cpm, 1.5A @ 24V DC: 10^5 Height : 97 mm Rating : Capacity, nominal: 1.5A @ 24V DC, Capacity, min 100 µA @ 100 mV DC, Power, max 41.4 W, Voltage, max 27.6V DC, Current, max 1.5 A Width : 94 mm Country of Origin : United States Module
Power dissipation, max : 8.7 W Power supply : 24V DC @ 350mA, Requires Class 2/SELV/PELV power supply Wiring category : 2 - on signal ports, 1 - on power and relay ports, 2 - on DeviceNet ports, 3 - on serial ports Data Handling
Accuracy, min : ±1% of full scale range for the channel, ±1% of alarm setpoint for speed Complex data : Spectra (synchronous or asynchronous), Waveform (synchronous or asynchronous), Simultaneous waveforms (synchronous), gSE Spectra Delta time buffer : Number of records: 2048, Delta time interval: 1…3600 s, Trigger mode: Relay is activated or trigger event (such as DeviceNet command from a controller or host) Spectra or waveform : Saved upon same trigger as delta time buffer - Downloads
Spec Sheet