Fuse CP 600VAC 250 MCM AL Heat Shrink Cable To Cable Amp-Trap®
MFG #CP250A1-HS
$1,413.35 / E
EACH
EACH
Product Description:
Mersen CP cable protectors are special purpose limiters which are crimped or bolted to cables to clear and isolate faults quickly, increasing the reliability of service entrance and distribution runs. They are current-limiting with a 200,000A interrupting rating, yet will carry low cable overloads which are handled by standard protective devices. Cable protectors are rated in terms of cable size and material (Al or Cu). Heat shrinkable (HS) tubing can be specified for field installation. For cables smaller than 4/0, class J fuses can be used.
HESCO Part Number
MERCP250A1HS
UPC
782001234362
Manufacturer Part Number
CP250A1-HS
Manufacturer
Mersen
Fuse CP 600VAC 250 MCM AL Heat Shrink Cable To Cable Amp-Trap®
MFG #CP250A1-HS
Product Description:
Mersen CP cable protectors are special purpose limiters which are crimped or bolted to cables to clear and isolate faults quickly, increasing the reliability of service entrance and distribution runs. They are current-limiting with a 200,000A interrupting rating, yet will carry low cable overloads which are handled by standard protective devices. Cable protectors are rated in terms of cable size and material (Al or Cu). Heat shrinkable (HS) tubing can be specified for field installation. For cables smaller than 4/0, class J fuses can be used.
HESCO Part Number
MERCP250A1HS
UPC
782001234362
Manufacturer Part Number
CP250A1-HS
Manufacturer
Mersen
$1,413.35 / E
EACH
EACH
- Specifications
Specifications
Rated voltage AC UL | : | 600 V |
Frequency (Hz) | : | 50/60 Hz |
AC or DC | : | AC |
Mounting | : | Crimp |
AC Max I.R./Breaking Capacity: I1 | : | 200 kA |
Design Details | : | 250 MCM AL Heat Shrink |
Connection/Terminal Material | : | Tin-Plated Aluminum |
Connection/Terminal Type | : | Cable To Cable |
Body/Insulating Material | : | GMG |
Length | : | 13.88 in |
Weight | : | 1.3 lb |
Specifications
Rated voltage AC UL : 600 V Frequency (Hz) : 50/60 Hz AC or DC : AC Mounting : Crimp AC Max I.R./Breaking Capacity: I1 : 200 kA Design Details : 250 MCM AL Heat Shrink Connection/Terminal Material : Tin-Plated Aluminum Connection/Terminal Type : Cable To Cable Body/Insulating Material : GMG Length : 13.88 in Weight : 1.3 lb